组合式过电压保护器参数额定电压UR的选择
确定组合式过电压保护器额定电压的主要依据是单相接地时健全相的最高暂时过电压 根据电力部1993年l0月30日《关于提高3 kV~66 kV无间隙金属氧化物避雷器额定电压和持续运行电压有关情况的通报》,对于6kV~10kV电机 ≥1.38 ,按国内标准,最高运行线电压为 =1.15 ,则6kV电动机的 =1.15~6.3=7.2(kV),6 kV电机过电压保护器的额定电压 ≥1.38~7.2=9.94(kV)。
The main basis for determining the rated voltage of the combined overvoltage protector is the maximum temporary overvoltage of the sound phase when single-phase grounding. According to the Circular of the Ministry of Electricity on 30 October 1993 on the Increase of the rated voltage and the continuous operating voltage of the 3 kV-66 kV gapless metal oxide arrester, for the 6 kV-10 kV motor (> 1.38). According to the domestic standards, the maximum operating line voltage is = 1.15, the 6 kV motor is = 1.15-6.3 = 7.2 (kV), and the rated voltage of the 6 kV motor overvoltage protector is more than 1.38-7.2 = 9.94 (kV).